TM 5-3825-270-23&P
0028
INSIDE OF
15-AMP
CONTROL PANEL
CIRCUIT BREAKER
20
1
1
15
5
5
EMERGENCY
10
10
10
STOP SWITCH
5
15
15
1
20
20
INTERCONNECT
POSITIVE
NEGATIVE
TERMINAL STRIP
TERMINAL STRIP
TERMINAL STRIP
Figure 5. Negative Terminal Strip - Step 3.
4.
CONDITION/INDICATION
Are less than 200 ohms measured from BATTERY VOLTAGE gauge harness connector pin 5 and negative
terminal strip terminal 17?
DECISION
No - Replace black wire between BATTERY VOLTAGE gauge harness connector, pin 5 and negative terminal
strip. (WP 0099) Verify problem is solved. (Step 4 - Does BATTERY VOLTAGE gauge operate?)
Yes - Replace BATTERY VOLTAGE gauge. (WP 0087) Verify problem is solved. (Step 4 - Does BATTERY
VOLTAGE gauge operate?)
STEP 4
Does BATTERY VOLTAGE gauge operate?
1.
Rotate EMERGENCY STOP switch to on position. (TM 5-3825-270-10)
2.
Observe BATTERY VOLTAGE gauge.
BATTERY
VOLTAGE GAUGE
Figure 6. Battery Voltage Gauge - Step 4.