TM 10-4630-206-12&P
UNIT MAINTENANCE
SEWAGE EJECTION PUMP, LAUNDRY
NSN 4630-01-413-2606
SEWAGE EJECTION PUMP, GENERAL PURPOSE
NSN 4630-01-413-2608
SEWAGE EJECTION PUMP, WASTE WATER EVACUATION
NSN 4630-01-505-3746
CIRCUIT BREAKERS
TEST, REPLACE
INITIAL SETUP
Tools
Personnel Required
Electrician
Tool Kit General Mechanics Automotive (Item 3, WP 0025 00)
Materials/Parts
Equipment Condition
Disconnect site power
All circuit breakers and switches
set to OFF
TEST
Test Circuit Breakers
WARNING
Proceed with caution when testing circuit breakers. Touching a live
wire or conductor can cause serious injury or death.
1. Open circuit breaker box (9-1-0150-1 and 9-1-0150-2)/control box (9-1-0527).
2. Turn circuit breaker OFF.
3. Remove and tag wires from circuit breaker (1) to be tested.
contacts (2). There should be a reading of infinity (Q).
5. If continuity is present, replace defective circuit breaker.
6. Turn circuit breaker ON.
contacts (2). There should be a reading of zero (0).
8. If no continuity is present, replace defective circuit breaker.
0015 00-1