Figure 7. Reset Button.
LOW OR NO OUTPUT FROM MUD CLEANING DISCHARGE PORT - MUD CLEANING SYSTEM (MCS)

Technical Manual For Water Well Drilling System (Wwds) - 2 Page Navigation
  261    262    263    264    265  266  267    268    269    270    271  
img
.
TM 5-3820-276-10-2
0174
NO ELECTRICAL POWER AT ONE OR MORE OUTLETS - MCS - Continued
CORRECTIVE ACTION - Continued
MALFUNCTION
2/3 Phase GFCI circuit breaker FAULT indicator illuminated.
CORRECTIVE ACTION
Verify if 2/3 Phase GFCI circuit breaker FAULT indicator is illuminated (Figure 8).
CIRCUIT
EMERGENCY
BREAKERS
STOP SWITCH
ELECTRICAL
2/3 PHASE GFCI
OUTLETS WWDS00852
CIRCUIT BREAKER
Figure 8.
2/3 PHASE GFCI Circuit Breaker.
a.
If illuminated, push RESET button. Verify if power is present at electrical outlets.
b.
If not illuminated, shut down APU (Volume 1, WP 0054) and shut down engine (Volume 1,
WP 0050). Notify maintenance.
END OF WORK PACKAGE
0174-6