TM 5-3820-276-10-2
0174
NO ELECTRICAL POWER AT ONE OR MORE OUTLETS - MCS - Continued
MALFUNCTION
GFCI circuit breaker tripped.
CORRECTIVE ACTION
Verify if RESET button on applicable electrical outlet is tripped (out) and/or red LED flashes
(Figure 7).
ELECTRICAL
OUTLETS
RED
LEDS
RESET
BUTTON(S)
WWDS00853
Figure 7.
Reset Button.
a.
If tripped (out), push RESET button. Verify if power is present at electrical outlets.
b.
If red LED flashes, GFCI electrical outlet requires replacement. Notify maintenance.
c.
If GFCI outlet is not tripped (out) and red LED is not flashing, notify maintenance.
0174-5