TM 10-4930-204-13(1) Clean metal parts with drycleaning solvent (item 1,App . F), and dry thoroughly.Clean hose surface with a clean, dry,cloth .(2) Inspect(3) Replacec.Installation.bonding wires.4-32.FUEL DISPENSINGnozzles for signs of deterioration and wear.defective nozzles, as necessary.Refer to figure 4-6 and install nozzles andHOSE REEL ASSEMBLY.a.General.The two hose reels have a recoil tension spring towind the 40-foot discharge hoses on. the reels.The product enterseach reel from the filter/separator through a pipe at the hub of thereel and is discharged through the hoses.b.Removal.NOTERemove hoses from reels (para 4-20) and releaserecoil spring tension before removing reels.(1) Pull dischargewound from reels.Disconnect(2) Release spring(12 turns).hoses out until they are completely un-hoses.tension on reel by turning reel backwardDo not disassemble spring housing as the springis under tension and can cause serious injury ordeath.(3) Refer to figure 4-30 (model as applicable) and removethe hose reels, hose rollers and spring housing.c.Cleaning andInspection.Drycleaning solvent normally has a flash pointof either 100 or 138 degrees F, depending on thetype being used, but may flash at much lower tem-peratures if contaminated with gasoline or jetfuel.Avoid repeated and prolonged skin contact.Do not use near open flame or excessive heat.4-57