TM 10-4930-236-13&Pf.Provide a suitable container beneath the filter/separator drain hose (8), open drain valve (9) and drainfuel from filter/separator (10) and hoses (11, 12,13 and 14).WARNINGFuel spills create a potential fire hazard. Use a drip pan beneath hoses whendisconnecting.g.To remove any of hoses (11, 12 or 13), pull out on cam lock arms (15) and disconnect hose.h.To remove hoses (14 and 16), pull out on cam lock arms (17) to disconnect hoses at filter/separatorand manifold, then refer to paragraph 4-13 and remove the EMD Pump Assembly (18).i.Pull out on cam lock arms (19) and disconnect hoses (14 and 16).j.Remove any of the gaskets (20) that require replacement.INSTALLATIONa.Make sure each female coupling has a good gasket (20) installed.b.Connect hoses (14 and 16) to EMD Pump Assembly (18) and close cam lock arms (19). Refer toparagraph 4-13 and install pump assembly.c.Connect hoses (14 and 16} at filter/separator and manifold and close cam lock arms (17).d.Install hoses (11, 12 and 13) and close cam lock arms (15).WARNINGA spring loaded mechanism can cause injury if released in an uncontrolledmanner. The rewind spring is under high tension when the dispensing hose isextended. This may cause reel to rapidly rotate in reverse.e.Connect reel hoses (2) and close cam lock arms (6). Install lockwire (5) and wind hose onto reel.f.Connect nozzle (3) to hose (2) and close cam lock arms (7).g.Make sure that drain valve (9) is closed.4-16