TM 10-4320-307-24
2-12.3 INSTALLATION OF GROUNDING ASSEMBLY.
a.
Remove grounding rods and cables from storage position.
b.
Install grounding assembly as follows:
NOTE
The earth surrounding ground rods must be moist to make a good electrical connection. In dry
or sandy areas, pour water around the rods to improve the connection.
(1)
Drive grounding rods (1) Into ground within 6 feet of each skid grounding pad (2) (one pad on each side
of skid).
(2)
Drive ground rods (1) to a minimum depth of 2-1/2 feet (0.762 m) into the ground.
(3)
Connect each skid grounding pad to corresponding grounding rod using the 6-foot uninsulated grounding
wire (3). Be sure connectors (4) have made tight electrical connection.
2-11