Figure 1. Low Tank Level Switch Harness Connector - Step 1.
Figure 4. Interconnect Terminal Strip - Step 2.

Field Maintenance Manual Tools List For Engineer Mission Module - Water Distributor Page Navigation
  277    278    279    280    281  282  283    284    285    286    287  
img
. .
TM 5-3825-270-23&P
0048
CONTROL PANEL
FACEPLATE SCREWS
Figure 2. Control Panel Faceplate Screws - Step 2.
2.
Disconnect green/white wire from interconnect terminal strip, terminal 12.
INSIDE OF
15-AMP
CONTROL PANEL
CIRCUIT BREAKER
20
1
1
15
5
5
EMERGENCY
10
10
10
STOP SWITCH
5
15
15
1
20
20
INTERCONNECT
POSITIVE
NEGATIVE
TERMINAL STRIP
TERMINAL STRIP
TERMINAL STRIP
Figure 3. Interconnect Terminal Strip - Step 2.
3.
Connect batteries. (WP 0085)
4.
Rotate EMERGENCY STOP switch to on position. (TM 5-3825-270-10)
5.
Set multimeter to measure voltage.
6.
Connect red multimeter probe to black wire at interconnect terminal strip, terminal 12.