TM 10-4930-236-13&P
Section III OPERATION UNDER USUAL CONDITIONS
Paragraph
Page
2-3
Grounding Procedures .................................................................................
2-12
2-4
Operating Procedures ..................................................................................
2-13
2-5
Preparation for Movement ...........................................................................
2-20
2-6
Operating Instructions on Decals and Instruction Plates ...............................
2-21
2-3. Grounding Procedures.
WARNING
Failure to properly ground unit prior to operation could allow a
static discharge (spark) which could ignite fuel or cause an
explosion of fuel vapor.
a.
Unwind the grounding cable and clamp from the static reel.
b.
Attach clamp to established ground. If established ground is not available, remove grounding rod from
pump unit frame.
c.
Use slide hammer to drive grounding rod 3 feet into ground then attach clamp to grounding rod.
d.
Once fueling operations are completed, disconnect clamp from grounding rod and guide cable back on reel.
e.
Use slide hammer to withdraw grounding rod from ground then place it in storage position on A-Frame and
secure with attaching straps.
2-12