TM 10-4930-236-13&POPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICESB - BeforeD - DuringA - AfterW - WeeklyM - MonthlyINTERVALPROCEDURESEQUIPMENT ISITEMITEM TO BECHECK FOR AND HAVE REPAIREDNOT READY/NOBD AWMINSPECTEDOR ADJUST AS NECESSARYAVAILABLE IF:16***Tank AssemblyVisual inspection to check for damage orEvidence ofsigns of leakage. Check for proper leakage oroperation of bottom loading valve. Referbottomto higher level of maintenance for repairloading valveor replacement of defective parts.will not open.17**ManholeCheck for damage and proper locationEvidence ofof manhole cover gasket, and securefuel leakagemanhole latches. Check the location ofexists.vent valve under handle, close to hinge.Refer to next higher level of maintenancefor repairs.18***Coupling HalfCheck for signs of leakage around theEvidence ofvalve handle shah. Check couplingleakage.gasket for cracks. Inspect coupling forsecure connection. Test coupling half byobserving the internal valve mechanismas the handle is moved to ensure handleoperates valve. Refer to next higherlevel of maintenance for repairs orreplacement if necessary.19**Grounding RodCheck for missing or damaged groundGround rodrod.missing.2-11