WATER HOSE OUTPUT LOW
Figure 3. Valve V5 - Step 2.

Technical Manual For Engineer Mission Module - Water Distributor Page Navigation
  222    223    224    225    226  227  228    229    230    231    232  
img
. . .
TM 5-3825-270-10
0064
VALVE V7
Figure 2. Valve V7 - Step 1.
CONDITION/INDICATION
Are valve V1 and valve V7 completely open?
DECISION
No - Completely open valve V1 and valve V7. (WP 0017) Verify problem is solved. (Step 5 - Is water hose
pressure normal (no more than 20% below normal)? Refer to Equipment Description and Data (WP 0002) for
normal pressure readings.)
Yes - Go to step 2. (Step 2 - Is valve V5 completely closed?)
STEP 2
Is valve V5 completely closed?
Verify valve V5 position.
0064-2