TM 5-4320-302-144-30.COOLING AIR BLOWER AND COOLING AIR DUCTING (CONT)Location/ItemActionRemarksREMOVAL1.Air cowlingLoosen two bottom fasteners and remove.2.Blower jacketRemove blower jacket screws and washersfrom blower jacket.3.Cooling airRemove from inside cooling air ducting.blower4.Right staya.Remove right stay plate bottom hex boltplateand washer.b.Remove right stay plate top hex bolt,washers, right stay plate bottom, andwashers.c.Remove right stay plate.5.Bottom covera.Remove bottom cover plate hex boltplateand washers.b.Remove bottom cover plate.6.Left staya.Remove bottom, side, and top hex bolts,plateand washers.b.Remove left stay plate.4-143