TM 5-4320-302-14
Table 4-1. Organizational Preventive Maintenance Checks and Services
W-Weekly
Q-Quarterly
M-Monthly
S-Semiannually
INTERVAL
ITEM
NO.
W
M
Q
S
ITEM TO BE INSPECTED
PROCEDURES
Place cover over gasket and strainer. Mate cover to fuel feed
pump. Thread screw into pump. Tighten screw securely.
WARNING
Priming discharge mixture of water and exhaust
gases may cause severe burns or injury. Wear
gloves and safety glasses when priming pump.
· Stand clear of venturi during priming.
Prime the centrifugal pump as soon as possible
after engine starts. Rotation of impeller without
water in volute will damage pump components.
Start engine and observe fuel feed pump for leaks.
4-17