TM 5-3825-270-10
0062
VALVE
V5
Figure 2. Valve V5 - Step 4.
CONDITION/INDICATION
Is valve V5 completely closed?
DECISION
No - Fully close valve V5. (WP 0018) Verify problem is solved. (Step 5 - Do sprinkler heads have appropriate
pressure (no more than 20% below normal)? Refer to Equipment Description and Data (WP 0002) for normal
pressure readings.)
Yes - Notify maintenance personnel sprinkler heads have low pressure.
STEP 5
Do sprinkler heads have appropriate pressure (no more than 20% below normal)? Refer to Equipment
Description and Data (WP 0002) for normal pressure readings.
CONDITION/INDICATION
Do sprinkler heads have appropriate pressure (no more than 20% below normal)? Refer to Equipment
Description and Data (WP 0002) for normal pressure readings.
DECISION
No - Notify maintenance personnel sprinkler heads have low pressure.
Yes - Problem solved.
END OF WORK PACKAGE