TM 10-4320-344-24
2.16.21 Fuse Holder Replacement, Model US636HCCD-1.
This task covers:
2.16.21.1 Removal
2 .
1
6 .2 1 . 2 I n s t a l l a t i on
INITIAL SETUP
Tools
Equipment Conditions
(Continued)
General Mechanics Automotive
Tool Kit, Appendix B, Section III,
Item 1
Material/Parts
Tags, Appendix C, Item 31
Equipment Conditions
Pumping station shut down,
TM 10-4320-344-10.
Control Panel Cover Assembly removed,
paragraph 2.16.2.
General Safety Instructions
To prevent rolling or sliding, do not work
on equipment that is not securely
s t a b i l i z e d.
Do not work on equipment with battery
connected. Electrocution hazard is
present if battery is connected.
Battery disconnected, paragraph
Do not work on equipment without following
2 .
1
5 .
4.
standard shop safety precautions.
2.16.21.1 Removal.
Figure 2-72. Fuse Holder Replacement.
Do not work on equipment with battery connected. Electrocution hazard is
present if battery is connected. Failure to obey this warning may result in
death or serious personal injury.
a .
Tag and disconnect two wires (Figure 2-72, 1).
b .
Unscrew and remove cover (2) and fuse (3).
c .
Remove nut (4), flat washer (5), and fuse holder (6) from control panel (7).
2-185